2001-01-08 00:00:001) SERVICE STATION NUMBER # 2 IS TO
 BE RELOCATED AWAY FROM EXIT DOOR
 LEADING TO STAIRS. NFPA 101, SECTION
 5-1.7.3 REQUIRES THAT MEANS OF EGRESS
 SHALL BE FREE OF OBSTRUCTIONS WHICH
 WOULD PREVENT ITS USE.
 2) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 3) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 4) SUBMIT COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. A SEPARATE PLAN AND
 PERMIT REQUIRED.
 5) PLEASE INDICATE WHERE EMERGENCY
 LIGHTING FIXTURES ARE LOCATED IN
 THE SEATING AREA.