2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRST SET OF NOTES.
 PLEASE "SHOW" LOAD CALCULATIONS. EG
 SQ. FT AND THE BREAKDOWN FOR LOADS AT
 125%. PLEASE SHOW BEFORE AND AFTER.
  
 2)NOTE: PLEASE MAKE MINOR CORRECTION FOR
 TOTAL KVA ON "K1"
  
 3)NOTE: PLEASE MAKE CORRECTION FOR PANEL
 REF. AS "H2A" SHOULD BE "H1A"
  
 4)NOTE: PLEASE SEE SHEET E 3.1 THERE IS
 A NOTE FOR TRANSFORMER TO SEE E-01??
 IS THIS THE NOTE/ DETAIL ON E5-1?
 PLEASE CALRIFY.
  
 5)NOTE: PLEASE SEE "K1" NOTE ADDED LOAD
 EXCEEDS LOAD SHOWN ON "K2" FOR TOTAL
 LOAD.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  