| Plan Review Notes For Permit 00070571 |
| Permit Number |
00070571 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE DAMPER DETAIL AND LOCATION. | | | 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89. | | | 4.REQUIRE SUPPLY AIR DIFFUSER SCHEDULE. | | | 5.REQUIRE EXHAUST FANS DETAIL FOR BATH- | | | ROOMS. | | | 6.REQUIRE EER RATING FOR AHU PER FLORIDA | | | ENERGY EFFICIENCY CODE. | | | 7.PROVIDE INFORMATION ON THE AHU ON PLAN | | | 8.PROVIDE RETURN AIR SCHEDULE. | | | ***NOTES*** | | | SEPERATE PERMIT IS REQUIRED FOR HOOD, | | | WALK-IN COOLERS FIRE SUPPRESSION SYSTEM, | | | FUEL. | | | PROVIDE INFORMATION ON THE EXHAUST FANS | | | FOR HOODS. | | | PROVIDE OUTSIDE AIR AND EXHAUST CLEAR- | | | ANCES FOR HOODS. |
|