Plan Review Notes
Plan Review Notes For Permit 00070571
Permit Number 00070571
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE SPRINKLER DRAWING DOES NOT SEEM
 TO INDICATE COMPLETE COVERAGE. ENTIRE
 SPACE TO BE PROTECTED BY FIRE SPRINKLERS
 INCLUDING COOLERS, FREEZERS, BATHROOMS,
 ELECTRICAL, JANITOR CLOSETS. NO
 HYDRAULIC CALCULATIONS PROVIDED.
 2) IDENTIFY MAIN EXIT CAPABLE OF
 EXITING AT LEAST 50 PERCENT OF THE
 OCCUPANT LOAD.
 3) ALL DOORS USED FOR EXITING TO BE
 EQUIPPED WITH APPROVED PANIC HARDWARE.
 FIRE DOORS USED FOR EXITING TO BE
 EQUIPPED WITH APPROVED FIRE EXIT
 HARDWARE.
 4) INTERIOR FINISH SHALL BE CLASS A OR
 B IN EXITS. OTHER AREAS CLASS A,B, OR
 C.
 5) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE HOOD, DUCT AND EXTINGUISHING SYSTEM.
 WET CHEMICAL FIRE EXTINGUISHING SYSTEMS
 ARE ONLY SYSTEMS ALLOWED.
 6) DUCT SMOKE DETECTOR(S) REQUIRED IN
 HVAC SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, HVAC SYSTEMS SHALL SHUT
 DOWN.
 7) NATURAL GAS INSTALLATION TO COMPLY
 WITH NFPA 54.
 8) PROVIDE DETAILS ON EXIT STAIR USED
 FOR EXITING.
 9) IDENTIFY ANY WAITING AREAS PLANNED
 FOR USE BY THE SPACE.
 10) PROVIDE FLAMESPREAD INFORMATION
 ON FOAM RUBBER BOOTH MATERIALS.
 11) EXPLAIN SERVICE STATION TWO AND
 HOW IT DOES NOT INTERFERE WITH
 EXITING.
 12) WHERE IS THE FIRE ALARM EQUIPMENT
 LOCATED.
 13) OCCUPANT LOAD TO BE DETERMINED
 BY THIS OFFICE.