2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE INDIACATE ALL BRANCH
 CIRCUIT #`S ON PLANS FOR ALL.
  
 2)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/CCONDENSING UNITS.
  
 3)NOTE: PLEASE NOTE THE REQ`MENT FOR
 OUTLET SPACING FOR LOCAL CODES. 210-50
  
 4)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED.???
 PLEASE SUBMIT LOAD CALCS.
 PLEASE SUBMIT PANEL SCHEDULE FOR PANEL
 "KDP" NOT SHOWN?? PLEASE SUBMIT THE AIC
 RATINGS FOR PANEL "KDP" AND SUBMIT
 RATING FOR MAIN DISCONNECT. MAINS/PANELS
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110-9
 PLEASENOTE THAT ALL LOAD CALCULATIONS
 ARE TO BE SHOWN. ALLCONTINUOUS LOADS
 ARE TO BE FIGURED AND SHOWN AT 125%
 (LIGHTING ) ETC.
  
 5)NOTE: PLEASE SEE PLANS AND SEE THAT
 YOU ARE SHOWING TWO DIFFERENT VOLTAGES
 COMING FROM "KDP" ???? PLEASE SHOW HOW
 THIS IS BEING DONE. TRANSFORMER???
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW