 ***************UNSAT********************
  
 1)PROVIDE COMPLETED FLORIDA ENERGY
 SHEETS WITH REQUIRED SEAL AND SIGNATURES
  
 2)FIRE SPRINKLER CONTRACTOR MUST SECURE
 PERMIT PRIOR TO ISSUANCE OF THE BUILDING
 PERMIT.
  
 3)PROVIDE CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR IMPACT
 RESISTANT WINDOWS AND DOORS.
  
 4)PROVIDE LIFE SAFETY PLAN THAT SHOWS
 CONTINUATION OF REAR EXIT FROM TENNANTS.
  
 5)KEY PLAN IS NOT CORRECT TO PLAN OF
 CITY PLACE.
  
 6)SHEET A.07 REFERENCES A-15 WHICH IS
 NOT SUPPLIED.
  
 7)SECOND SHEET A.01 REFERENCES DOORS AND
 TOILETS. IS THIS SHEET MISNUMBERED?
  
 8)ALL WOOD BUCKS, HEADERS, BLOCKING, ETC
 IN PARTITIONS, TO BE APPROVED FIRE
 RETARDANT TREATED LUMBER.
  
 9)PROVIDE FIRE RATING ON FOAM BOARD ON
 SHEET A-03 FOR ASSEMBLY OCCUPANCY.
  
 10)PROVIDE LETTER FROM SPECIAL INSPECTOR
 THAT WORK IS READY TO BEGIN.
  
 11)SEPARATE PERMIT IS REQUIRED FOR SIGNS
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8392
  
 FRANK KNAPP
 BUILDING PLAN REVIEW