Plan Review Notes
Plan Review Notes For Permit 00070560
Permit Number 00070560
Review Stop R
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS:
 -INFORMATION SUBMITTED IS MISSING THE
 APPROVED DRAWINGS REFERENCED IN THE
 PRODUCT APPROVAL.
 -INSTALLATION SCHEDULE AND KEY PLAN
 DON'T MATCH. SEE FLOOR PLAN.
 -INFORMATION GIVEN IN THE INSTALLATION
 SCHEDULE IS NOT CLEAR. EG: SPECIFIC
 ANCHOR TO BE USED ACCORDING TO THE
 STRUCTURE TO BE ATTACHED TO (MASONRY
 OR WOOD). SHUTTER SPAN (VERTICAL OR
 HORIZONTAL.
 2-EGRESS WINDOWS TO HAVE 24" MINIMUM
 CLEAR HEIGHT OPENING AS PER SECTION
 1005.4.4 SBC 1997.
 NOTE: TO BE FIELD VERIFIED AFTER
 WINDOW INSTALLATION.