| Plan Review Notes For Permit 00070560 |
| Permit Number |
00070560 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS: | | | -INFORMATION SUBMITTED IS MISSING THE | | | APPROVED DRAWINGS REFERENCED IN THE | | | PRODUCT APPROVAL. | | | -INSTALLATION SCHEDULE AND KEY PLAN | | | DON'T MATCH. SEE FLOOR PLAN. | | | -INFORMATION GIVEN IN THE INSTALLATION | | | SCHEDULE IS NOT CLEAR. EG: SPECIFIC | | | ANCHOR TO BE USED ACCORDING TO THE | | | STRUCTURE TO BE ATTACHED TO (MASONRY | | | OR WOOD). SHUTTER SPAN (VERTICAL OR | | | HORIZONTAL. | | | 2-EGRESS WINDOWS TO HAVE 24" MINIMUM | | | CLEAR HEIGHT OPENING AS PER SECTION | | | 1005.4.4 SBC 1997. | | | NOTE: TO BE FIELD VERIFIED AFTER | | | WINDOW INSTALLATION. |
|