Plan Review Notes
Plan Review Notes For Permit 00070560
Permit Number 00070560
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SECOND CHECKLIST:
 1-BEDROOM WINDOWS DON'T COMPLY WITH THE
 MINIMUM EGRESS REQUIREMENTS OF SECTION
 1005.4.4 OF SBC 1997. A 24 SINGLE HUNG
 WINDOW DOESN'T PROVIDE 24" MINIMUM
 CLEAR HEIGHT OPENING. ALSO,PGT DOESN'T
 HAVE ANY 4'-4" HIGH WINDOW AS SHOWN ON
 ARCHITECT'S DRAWINGS.
 REVISE DRAWINGS AS REQUIRED.
 2-STORM PANELS:
 -PROVIDE KEY PLAN INDICATING WINDOWS OR
 DOORS TO RECEIVE STORM PANELS.
 -CLEARLY INDICATE TYPE OF CONSTRUCTION
 TO RECEIVE STORM PANELS. WOOD OR
 CONCRETE BLOCK BECAUSE ANCHOR TYPE AND
 SPACING IS DIFFERENT.
 -ALSO TAKE INTO CONSIDERATION THAT
 ANCHOR SELECTED IS TO BE EMBEDED INTO
 THE CONCRETE BLOCK OR WOOD. ANCHORS
 ARE NOT GOOD TO BE ATTACHED TO BRICK.
 -CLEARLY SPECIFY ANCHOR TYPE IN THE
 INSTALLATION SCHEDULE. ALSO, REVISE
 THE SHUTTER SPAN.
 -PROVIDE COPIES OF THE APPROVED DWGS AS
 SPECIFIED ON THE PRODUCT APPROVAL
 REPORT AND HIGHLIGHT SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED.
 3-REVISE ENERGY CALCULATIONS:
 -PREDOMINANT EAVE OVERHANG IS NOT 2'-0"
 SEE EXTERIOR ELEVATIONS.
 -COMPLETELY FILL TABLE 6C-2.
 -SEE GENERAL DIRECTIONS AT THE BOTTOM
 OF PAGE TWO.
 -USE THE UPDATED BLANK SHEETS ATTACHED
 -TABLE 6C-3: CHECK ONLY THE ITEMS THAT
 APPLY TO THIS PROJECT.
 -OWNER TO SIGN AND DATE THIS FORM ALSO.
 4-PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLIONS.
 -PROVIDE PRODUCT APPROVAL WITH LEGIBLE
 DRAWINGS FOR FRENCH DOOR WITH SIDELITE
 AND SINGLE HUNG WINDOWS.
  
  
  
  
  
  
  
 NOTES:
  
 -PLEASE CALL JULIO GOMEZ AT 659-8096 EXT
 8232 IF YOU HAVE ANY QUESTIONS.
 -PLEASE RETURN REVIEWED SET AFTER ALL
 REVISIONS ARE DONE IN THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.