| Date |
Text |
| 2001-01-08 00:00:00 | SECOND CHECKLIST: |
| | 1-BEDROOM WINDOWS DON'T COMPLY WITH THE |
| | MINIMUM EGRESS REQUIREMENTS OF SECTION |
| | 1005.4.4 OF SBC 1997. A 24 SINGLE HUNG |
| | WINDOW DOESN'T PROVIDE 24" MINIMUM |
| | CLEAR HEIGHT OPENING. ALSO,PGT DOESN'T |
| | HAVE ANY 4'-4" HIGH WINDOW AS SHOWN ON |
| | ARCHITECT'S DRAWINGS. |
| | REVISE DRAWINGS AS REQUIRED. |
| | 2-STORM PANELS: |
| | -PROVIDE KEY PLAN INDICATING WINDOWS OR |
| | DOORS TO RECEIVE STORM PANELS. |
| | -CLEARLY INDICATE TYPE OF CONSTRUCTION |
| | TO RECEIVE STORM PANELS. WOOD OR |
| | CONCRETE BLOCK BECAUSE ANCHOR TYPE AND |
| | SPACING IS DIFFERENT. |
| | -ALSO TAKE INTO CONSIDERATION THAT |
| | ANCHOR SELECTED IS TO BE EMBEDED INTO |
| | THE CONCRETE BLOCK OR WOOD. ANCHORS |
| | ARE NOT GOOD TO BE ATTACHED TO BRICK. |
| | -CLEARLY SPECIFY ANCHOR TYPE IN THE |
| | INSTALLATION SCHEDULE. ALSO, REVISE |
| | THE SHUTTER SPAN. |
| | -PROVIDE COPIES OF THE APPROVED DWGS AS |
| | SPECIFIED ON THE PRODUCT APPROVAL |
| | REPORT AND HIGHLIGHT SPECIFIC MOUNTING |
| | CONDITIONS AND ANCHOR TYPE AND SPACING |
| | TO BE USED. |
| | 3-REVISE ENERGY CALCULATIONS: |
| | -PREDOMINANT EAVE OVERHANG IS NOT 2'-0" |
| | SEE EXTERIOR ELEVATIONS. |
| | -COMPLETELY FILL TABLE 6C-2. |
| | -SEE GENERAL DIRECTIONS AT THE BOTTOM |
| | OF PAGE TWO. |
| | -USE THE UPDATED BLANK SHEETS ATTACHED |
| | -TABLE 6C-3: CHECK ONLY THE ITEMS THAT |
| | APPLY TO THIS PROJECT. |
| | -OWNER TO SIGN AND DATE THIS FORM ALSO. |
| | 4-PROVIDE PRODUCT APPROVAL FOR WINDOW |
| | MULLIONS. |
| | -PROVIDE PRODUCT APPROVAL WITH LEGIBLE |
| | DRAWINGS FOR FRENCH DOOR WITH SIDELITE |
| | AND SINGLE HUNG WINDOWS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | NOTES: |
| | |
| | -PLEASE CALL JULIO GOMEZ AT 659-8096 EXT |
| | 8232 IF YOU HAVE ANY QUESTIONS. |
| | -PLEASE RETURN REVIEWED SET AFTER ALL |
| | REVISIONS ARE DONE IN THE ORIGINAL |
| | DRAWINGS IN ORDER TO EXPEDITE THE |
| | REVIEW PROCESS. |