Plan Review Notes
Plan Review Notes For Permit 00070557
Permit Number 00070557
Review Stop M
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1. DUCT SMOKE DETECTOR TO SENSE RETURN
 AIR CONDITION PRIOR TO ANY MIXING OF
 OUTSIDE AIR
 2. OUTSIDE AIR DUCT TO BE INCREASED TO
 7" FORM 6" AND VOLUME DAMPER TO BE 135
 NOT 80 PER D. ROMCKE ENG.
 3.NEW REVISION TO FOLLOW SHOWING THESE
 CHANGES ON PLAN