| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1. BATHROOM EXHAUST FAN TO BE INTERLOCK | | | W/ AHU OR ON ALL THE TIME-NOT TIED TO | | | LIGHT SWITCH | | | 2. OUTSIDE AIR CALCULATION DOES NOT MEET | | | ASHRAE 62-89 SQ.FT. X .30 | | | 3. DUCT SMOKE DETECTOR TO BE INSTALLED | | | IN RETURN AIR PRIOR TO ANY MIXING OF | | | OUTSIDE AIR PER 1997 SMC |
|