Plan Review Notes
Plan Review Notes For Permit 00070557
Permit Number 00070557
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE FIRE DAMPER DETAIL SMC 610.6.
 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 3.PROVIDE ENERGY EFFICIENCY RATING OF
 AHU PER FLORIDA ENERGY EFFICIENCY CODE
 4.REQUIRE DUCT MATERIAL SCHEDULE.
 5.FLEX DUCT CONNECTION DETAIL REQUIRED.
 NOTE:
 FAN SHUT-DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY BUILDING FIRE
 ALARM SYSTEM OR TIED TO HORN AND
 STROBE PER NFPA 90A 4.4.4.2 OR 4.4.4.3