| Plan Review Notes For Permit 00070557 |
| Permit Number |
00070557 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE FIRE DAMPER DETAIL SMC 610.6. | | | 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 3.PROVIDE ENERGY EFFICIENCY RATING OF | | | AHU PER FLORIDA ENERGY EFFICIENCY CODE | | | 4.REQUIRE DUCT MATERIAL SCHEDULE. | | | 5.FLEX DUCT CONNECTION DETAIL REQUIRED. | | | NOTE: | | | FAN SHUT-DOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION BY BUILDING FIRE | | | ALARM SYSTEM OR TIED TO HORN AND | | | STROBE PER NFPA 90A 4.4.4.2 OR 4.4.4.3 |
|