| Plan Review Notes For Permit 00070557 |
| Permit Number |
00070557 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW LOAD CALCULATION | | | GIVING BREAKDOWN OF TRACK LIGHTING PER | | | 220-12 | | | | | | 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | FOR TRANSFORMER AND POINT OF ATTACHEMENT | | | | | | 3)NOTE: PLEASE SHOW RECEPT IN BATH AS | | | GFI.210-8 | | | | | | 4)NOTE: PLEASE SEE LOCAL CODE FOR OUTLET | | | SPACING IN STOCK ROOM, AND TENANT SPACE. | | | 210-50. EVERY 20` OF WALL SPACE. | | | | | | 5)NOTE: PLEASE SHOW THE REQ`D OUTLETS | | | FOR SHOW WINDOWS 210-62 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|