| Plan Review Notes For Permit 00070544 |
| Permit Number |
00070544 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SECOND CHECKLIST: | | | 1-TAKE DRAWINGS TO PALM BEACH COUNTY. | | | THEY WILL VERIFY IF YOU NEED TO PAY | | | IMPACT FEES OR NOT. THEY WILL STAMP | | | THE DRAWINGS AND GIVE YOU A RECEIPT. | | | 2-WINDOWS AT SECOND FLOOR BEDROOMS DON'T | | | COMPLY WITH THE MINIMUM EGRESS | | | REQUIREMENTS ON SECTION 1005.4.4 OF | | | SBC 1997. | | | 3-PROVIDE 2 COPIES OF PRODUCT APPROVALS. | | | -CLEARLY SPECIFY/HIGHLIGHT IF USING | | | WINDOWS WITH MISSILE IMPACT GLAZING OR | | | NOT. PRODUCT APPROVAL HAS BOTH OPTIONS | | | -PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOOR. | | | NOTE:ENTRY DOOR SHOWS GLASS. HOW IS IT | | | PROTECTED FROM MISSILE IMPACTS. | | | 4-SEE COMMENTS ON PLANS AND REVISE/ | | | UPDATE DRAWINGS AS REQUIRED. PROVIDE | | | CLARIFICATIONS AS REQUESTED. | | | 5-PROVIDE LINTEL SCHEDULE AT ALL NEW | | | OPENINGS. SEC 104.2.2 CITY AMENDMENTS. | | | 6-PROVIDE SAFETY GLASS AT MASTER BATHRM. | | | SECTION 2405.2 SBC 1997. | | | 7-PROVIDE ENERGY CALCULATIONS AND MANUAL | | | J CALCULATIONS. | | | -PROVIDE A/C DRAWINGS. | | | | | | | | | | | | | | | | | | NOTE: | | | -PLEASE RETURN REVIEWED SETS AFTER | | | CORRECTIONS ARE DONE IN ORDER TO | | | EXPEDITE THE REVIEW PROCESS. |
|