2001-01-08 00:00:00CHECKLIST:
 1-TAKE DRAWINGS TO THE PALM BEACH COUNTY
 TO VERIFY IF YOU NEED TO PAY IMPACT
 FEES. THEY WILL STAMP DRAWINGS & GIVE
 YOU A RECEIPT.
 2-WILL NEED A NOTICE OF COMMENCEMT TO
 BE FILED AT THE COURTHOUSE.
 3-WINDOWS AT SECOND FLOOR BEDROOMS DON'T
 COMPLY WITH EGRESS REQUIREMENTS SECT'N
 1005.4.4 SBC 1997.
 4-SEE COMMENTS BY HISTORIC PRESERVATION
 DIVISION AND REVISE PLANS ACCORDINGLY.
 5-LEGIBLY PROVIDE THE NAME, ADDRESSAND
 LICENSE NUMBER OF ARCHITECT.
 -ARCHITECT TO DATE DRAWINGS AT TIME OF
 SEALING THEM.
 FLORIDA STATUTES CHAPTER 481.
 6-PROVIDE 2 COPIES OF PRODUCT APPROVALS.
 NOTE: SPECIFY IF USING MISSILE IMPACT
 GLAZING WINDOWS AND DOORS OR IF USING
 STORM SHUTTERS.
 7-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE DRAWINGS AS REQUIRED.
 8-PROVIDE LINTEL SCHEDULE AT ALL NEW
 OPENINGS. SEC 104.2.2 CITY AMENDMENTS.
 9-PROVIDE SAFETY GLASS AT SECOND FLOOR
 BATHROOMS. SEC. 2405.2 SBC 1997.
 10-WHERE IS THE ATTIC ACCESS PANEL FOR
 SECOND FLOOR ROOF? SEC 2309.6 SBC 1997
 11-FILL IN THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM.ATTACHED
 12-PROVIDE THE DESIGN PRESSURES
 CALCULATED AT ALL EXTERIOR OPENINGS.
 SECTION 1606 SBC 1997.
 13-PROVIDE A/C DRAWINGS, ENERGY CALCS
 AND MANUAL J CALCULATIONS.
  
  
  
  
 NOTE:
  
 -PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.