| Plan Review Notes For Permit 00070544 |
| Permit Number |
00070544 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE:PLEASE NOTE THE REQ`D SMOKE | | | DETECTOR PER NFPA-72 2-2.1.1.1 REQ`D | | | DOWNSTAIRS | | | | | | 2)NOTE: PLEASE REVISE PANEL SCHEDULE AND | | | LIST THE REQ`D DEDICATED BATH(S) CIRCUIT | | | PER 210-11-C-3/210-52D | | | | | | 3)NOTE: PLEASE NOTE AND SHOW ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECTED. PER 210-8-A-6 | | | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | MAIN/PANEL. ALL EQUIPMENT MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER | | | 110-9 OF THE NEC. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORAMTION | | | FOR REVIEW BEFORE ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE AREN | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|