Plan Review Notes
Plan Review Notes For Permit 00070544
Permit Number 00070544
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE:PLEASE NOTE THE REQ`D SMOKE
 DETECTOR PER NFPA-72 2-2.1.1.1 REQ`D
 DOWNSTAIRS
  
 2)NOTE: PLEASE REVISE PANEL SCHEDULE AND
 LIST THE REQ`D DEDICATED BATH(S) CIRCUIT
 PER 210-11-C-3/210-52D
  
 3)NOTE: PLEASE NOTE AND SHOW ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. PER 210-8-A-6
  
 4)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 MAIN/PANEL. ALL EQUIPMENT MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER
 110-9 OF THE NEC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMTION
 FOR REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE AREN
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372