Plan Review Notes
Plan Review Notes For Permit 00070527
Permit Number 00070527
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW REF SPC 94
 (1A) SHT A-1 ACCESS TO H/C REST RM'S
 THRU A STORAGE ROOM, IS NOT ACCESSIBLE
 TO THE PUBLIC AS REQUIRED.
 COMPLY W/FACBC 4.1.3 (11)
 (B) 1 DRINKING FOUNTAIN REQ. TAB 407, TO
 COMPLY W/FACBC 4.1.3 (10), PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
 (C) A/C CONDENSATE DRAIN, CONNECT TO
 COMMON SYSTEM FURNISHED BY OWNER.
 NOT TO SANITARY SEWER.
 END OF COMMENTS