| Plan Review Notes For Permit 00070527 |
| Permit Number |
00070527 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR HYDRAULIC | | | CLACULATIONS PROVIDED IN DRAWINGS. | | | LEGEND ON PAGE E-2 DISPLAYS FIRE | | | SPRINKLER HEADS BUT NONE COULD BE | | | LOCATED. | | | 2) EXITING THROUGH STOCKROOM PERMITTED | | | IF NOT MORE THAN 50 PERCENT OF EXIT | | | ACCESS IS PROVIDED THROUGH STOCKROOM, | | | A 44" AISLE IS REQUIRED, THE DOOR | | | LEADING TO THE STOCKROOM CANNOT BE | | | LOCKED, AND THE 44" AISLE BE MAINTAINED. | | | 3) DOOR LEADING INTO STOCKROOM NEEDS | | | TO BE REVERSED. DOOR SHOULD SWING | | | INTO STOCKROOM. | | | 4) INTERIOR FINISH ON WALLS AND CEILINGS | | | SHALL BE CLASS A OR B. | | | 5) NO INFORMATION PROVIDED ON | | | FIRESTOPPING. |
|