| Plan Review Notes For Permit 00070516 |
| Permit Number |
00070516 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | | | | PROVIDE AIR BALANCE PER 1997 SMC 501.2.. | | | PROVIDE DAMPER DETAIL AND LOCATION ON | | | PLANS. | | | REQUIRE DUCT MATERIAL SCHEDULE. | | | GRILLE SCHEDULE TO BE PROVIDED. | | | FLEX DUCT CONNECTION DETAIL REQUIRED. | | | ENERGY EFFICIENCY RATING OF THE AHU IS | | | REQUIRED PER FLORIDA ENERGY EFFICIENCY | | | CODE. | | | FAN SHUTDOWN IS REQUIRED PER NFPA 90A | | | 4.4.4.2 & 4.4.4.3... |
|