| Plan Review Notes For Permit 00070516 |
| Permit Number |
00070516 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH ON WALLS AND | | | CEILINGS SHALL BE CLASS A OR B. CURTAINS | | | SHOWN HANGING ARE WHAT FLAME SPREAD | | | RATING. | | | 2) NO ILLUMINATED EXIT SIGN SHOWN AT | | | DOOR LEADING INTO STOCKROOM FROM | | | SALES AREA. | | | 3) HOW IS THE BASE BUILDING FIRE ALARM | | | SYSTEM HEARD IN TENANT SPACE. NO FIRE | | | ALARM EQUIPMENT SHOWN ON POWER PLAN. | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 5) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED IN | | | DRAWINGS. | | | 6) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS ARE MET, | | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS PERMITTED THROUGH STOCKROOM, THE DOOR | | | LEADING TO STOCKROOM CANNOT BE LOCKED, | | | AISLE OF AT LEAST 44" WIDE REQUIRED IN | | | STOCKROOM, THIS 44" AISLE TO BE | | | MAINTAINED. |
|