| 2001-01-08 00:00:00 | ***************PROVISO *************** | | | | | | 1)NOTE:PLEASE PROVIDE AIC RATINGS FOR | | | ALL EQUIPMENT BEING INSTALLED. MAINS/ | | | PANELS. MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT. 110-9 | | | | | | 2)NOTE: PLEASE CLARIFY TOTAL LOAD ON | | | TRANSFORMER. ? | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCUALATIONS | | | WITH ALL CONTINUOUS LOADS SHOWN AT 125% | | | (LIGHTING ) ETC. | | | | | | 4)NOTE: PLEASE SHOW WINDOW OUTLETS PER | | | 210-62 LOAD TO BE FIGURED PER 220-12A | | | | | | 5)NOTE: PLEASE SHOW LOAD CALCS FOR TRACK | | | LIGHTING PER 220-12B . | | | | | | 6)NOTE: PLEASE CLARIFY CIRCUIT FOR SIGN. | | | PER 220-3-B | | | | | | | | | PLEAS SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | CITY OF WEST PALM BEACH | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|