Plan Review Notes
Plan Review Notes For Permit 00070516
Permit Number 00070516
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO ***************
  
 1)NOTE:PLEASE PROVIDE AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS/
 PANELS. MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT. 110-9
  
 2)NOTE: PLEASE CLARIFY TOTAL LOAD ON
 TRANSFORMER. ?
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALATIONS
 WITH ALL CONTINUOUS LOADS SHOWN AT 125%
 (LIGHTING ) ETC.
  
 4)NOTE: PLEASE SHOW WINDOW OUTLETS PER
 210-62 LOAD TO BE FIGURED PER 220-12A
  
 5)NOTE: PLEASE SHOW LOAD CALCS FOR TRACK
 LIGHTING PER 220-12B .
  
 6)NOTE: PLEASE CLARIFY CIRCUIT FOR SIGN.
 PER 220-3-B
  
  
 PLEAS SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372