Plan Review Notes
Plan Review Notes For Permit 00070488
Permit Number 00070488
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)GREASE INTERCEPTOR NOT PERMITTED IN
 FOOD PREP AREA.INTERCEPTOR MAY NOT BE
 REQD.CONTACT ROD COMPO W/CITY OF WPB
 WASTEWATER TREATMENT FACILITY AT (561)-
 835-7423 FOR WAIVER.SUBMIT COPY OF FORM.
  
 2)WATER CLOSETS AND LAVATORIES ARE NOT
 PROPERLY VENTED.COMPLY W/FACBC 901.2.
  
 3)FLOOR CLEANOUT SHALL BE ACCESSIBLE..
 710.2.3,710.3.
  
 4)3-COMP.SINK DRAIN SHALL BE MIN.2 PER
 TABLE 713.1.
  
 5)A SHUT-OFF VALVE IS REQD.ON THE WATER
 SUPPLY BRANCH PER SPC SEC.610.4.2.
  
 6)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 7)OVER 2 FIXTURES ARE SUPLLIED BY 1/2"
 COLD WATER.COMPLY W/COUNTYWIDE AMEND-
 MENTS TO SPC SEC.911.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.