| Plan Review Notes For Permit 00070488 |
| Permit Number |
00070488 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)GREASE INTERCEPTOR NOT PERMITTED IN | | | FOOD PREP AREA.INTERCEPTOR MAY NOT BE | | | REQD.CONTACT ROD COMPO W/CITY OF WPB | | | WASTEWATER TREATMENT FACILITY AT (561)- | | | 835-7423 FOR WAIVER.SUBMIT COPY OF FORM. | | | | | | 2)WATER CLOSETS AND LAVATORIES ARE NOT | | | PROPERLY VENTED.COMPLY W/FACBC 901.2. | | | | | | 3)FLOOR CLEANOUT SHALL BE ACCESSIBLE.. | | | 710.2.3,710.3. | | | | | | 4)3-COMP.SINK DRAIN SHALL BE MIN.2 PER | | | TABLE 713.1. | | | | | | 5)A SHUT-OFF VALVE IS REQD.ON THE WATER | | | SUPPLY BRANCH PER SPC SEC.610.4.2. | | | | | | 6)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | 7)OVER 2 FIXTURES ARE SUPLLIED BY 1/2" | | | COLD WATER.COMPLY W/COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.911. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|