2001-01-08 00:00:00******************DENIED****************
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3. FLOOR PLAN ON A1 DOES NOT MATCH M1
 DRAWING RE: RATED WALL @ R/A F/D.
 FIRE DAMPER TO BE INSTALLED PER SPECS
 NOT ANGLED IN DUCT AS SHOWN ON M1 FOR
 PROTECTION OF OPENING