| Plan Review Notes For Permit 00070488 |
| Permit Number |
00070488 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************DENIED**************** | | | | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3. FLOOR PLAN ON A1 DOES NOT MATCH M1 | | | DRAWING RE: RATED WALL @ R/A F/D. | | | FIRE DAMPER TO BE INSTALLED PER SPECS | | | NOT ANGLED IN DUCT AS SHOWN ON M1 FOR | | | PROTECTION OF OPENING |
|