| Plan Review Notes For Permit 00070488 |
| Permit Number |
00070488 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)TITLE SHEET-INCLUDE SPC 1994 EDITION. | | | | | | 2)DRINKING FOUNTAIN SHALL BE ACCESSIBLE | | | TO PATRONS WITHOUT RESTRICTION AND | | | COMPLY W/FACBC SEC.4.1.3.(10)(A),4.15. | | | SPC 407.2.2. | | | | | | 3)TOILET ROOM SHALL BE LOCATED ON AN | | | ACCESSIBLE ROUTE AND ACCESSIBLE ROUTE | | | SHALL BE CLEARLY DEFINED ON THE PLANS. | | | FACBC 4.1.3(11),4.2.1,4.3.1,4.3.2,(3), | | | 4.3.3. | | | | | | 4)TOILET ROOM SHALL BE AVAILABLE TO | | | PATRONS WITHOUT RESTRICTION DURING | | | NORMAL OPERATING HOURS PER SPC SEC. | | | 407.2.2. | | | | | | 5)PLANS SHALL BE ROUTED TO DEPT.OF | | | BUSINESS AND PROFESSIONAL REGULATION FOR | | | REVIEW AND APPROVAL.COUNTYWIDE AMENDMENT | | | TO SPC SEC.101.4.7.CALL 954-958-5520. | | | | | | 6)SUBMIT SIGNED,SEALED AND DATED WATER | | | AND SANITARY ISOMETRICS FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | 104.2.3.. | | | | | | 7)DISCHARGE OF FIXTURES OTHER THAN THE | | | TOILET ROOM SHALL BETO A GREASE | | | INTERCEPTOR PER SPC 1004.4. | | | | | | IF YOU HAVE ANY QUESTIONS CALL | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|