Plan Review Notes
Plan Review Notes For Permit 00070488
Permit Number 00070488
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 2.REQUIRE EXHAUST FANS DETAILS ON PLANS
 3.ENERGY EFFICIENCY RATING OF AHU IS
 REQUIRED PER FLORIDA ENERGY EFFICIENCY
 CODE.
 4.ENERGY CALCULATIONS NEEDS TO BE SIGNED
 AND SEALED.
 5.INDICATE FIRE/SMOKE DAMPERS WHERE
 APPLICABLE.
 6.SHOW SMOKE DETECTOR ON PLANS.