| Plan Review Notes For Permit 00070488 |
| Permit Number |
00070488 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 2.REQUIRE EXHAUST FANS DETAILS ON PLANS | | | 3.ENERGY EFFICIENCY RATING OF AHU IS | | | REQUIRED PER FLORIDA ENERGY EFFICIENCY | | | CODE. | | | 4.ENERGY CALCULATIONS NEEDS TO BE SIGNED | | | AND SEALED. | | | 5.INDICATE FIRE/SMOKE DAMPERS WHERE | | | APPLICABLE. | | | 6.SHOW SMOKE DETECTOR ON PLANS. |
|