Plan Review Notes
Plan Review Notes For Permit 00070488
Permit Number 00070488
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE SPRINKLER SECTION OF PLANS ARE
 NOT ACCEPTABLE. ACCORDING TO THE WATER
 SUPPLY GRAPH, ONLY 1.43 LBS IS AVAILABLE
 BETWEEN SUPPLY AND PRESSURE REQUIRED.
 WHERE DID THE SUPPLY DATA COME FROM.
 2) NO FIRE DAMPERS SHOWN ON PLANS.
 3) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF THE FOLLOWING CONDITIONS EXIST,
 DOOR LEADING TO STOCKROOM CANNOT BE
 LOCKED, AISLE THROUGH STOCKROOM TO
 BE AT LEAST 44" WIDE, THIS 44" AISLE
 TO BE MAINTAINED, AND EXIT CANNOT
 PROVIDE NO MORE THAN 50 PERCENT OF
 EXIT ACCESS.
 4) PROVIDE PLANS AND PERMIT FOR FIRE
 ALARM EQUIPMENT SHOWN IN SPACE. CUT
 SHEETS NEEDED ON ALL DEVICES.
 5) WHERE IS THE EMERGENCY LIGHTING IN
 THE SALES AREA.