| Plan Review Notes For Permit 00070488 |
| Permit Number |
00070488 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE SPRINKLER SECTION OF PLANS ARE | | | NOT ACCEPTABLE. ACCORDING TO THE WATER | | | SUPPLY GRAPH, ONLY 1.43 LBS IS AVAILABLE | | | BETWEEN SUPPLY AND PRESSURE REQUIRED. | | | WHERE DID THE SUPPLY DATA COME FROM. | | | 2) NO FIRE DAMPERS SHOWN ON PLANS. | | | 3) EXITING THROUGH STOCKROOM PERMITTED | | | ONLY IF THE FOLLOWING CONDITIONS EXIST, | | | DOOR LEADING TO STOCKROOM CANNOT BE | | | LOCKED, AISLE THROUGH STOCKROOM TO | | | BE AT LEAST 44" WIDE, THIS 44" AISLE | | | TO BE MAINTAINED, AND EXIT CANNOT | | | PROVIDE NO MORE THAN 50 PERCENT OF | | | EXIT ACCESS. | | | 4) PROVIDE PLANS AND PERMIT FOR FIRE | | | ALARM EQUIPMENT SHOWN IN SPACE. CUT | | | SHEETS NEEDED ON ALL DEVICES. | | | 5) WHERE IS THE EMERGENCY LIGHTING IN | | | THE SALES AREA. |
|