| Plan Review Notes For Permit 00070488 |
| Permit Number |
00070488 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO ************** | | | | | | NOTE: PLEASE SUBMIT LOAD CALCULAITON TO | | | CORRELATE OR CLARIFY LOADS SHOWN. PLEASE | | | SHOW WHAT THE LOADS ARE THAT YOU ARE | | | ADDING 20% FOR? IS THIS FOR THE 25% | | | OF CONTINUOUS LOADS? ARE YOU JUST ADDING | | | 20% FOR THE ENTIRE PANEL.? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|