Plan Review Notes
Plan Review Notes For Permit 00070484
Permit Number 00070484
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)DOOR FROM JANITOR'S CLOSET CANNOT
 SWING INTO CLEAR FLOOR SPACE FOR LAV.PER
 FACBC SEC.4.22.2.
  
 2)OFFICE DOOR SHALL NOT SWING INTO CLEAR
 FLOOR SPACE REQD.FOR DRINKING FOUNTAIN.
 FACBC 4.22.2.
  
 3)DRINKINGFOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 4)AN ADDITIONAL LAV.IS REQD.IN THE
 WOMEN'S R.R.PER TABLE 407.
  
 5)WATER CLOSETS ARE NOT PERMITTED ON WET
 VENT PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 6)BENCH IN FITTING ROOM SHALL BE LOCATED
 ALONG WALL W/THE LONGER DIMENSION PER
 FACBC SEC.4.35.4.
  
 7)RELIEF LINE SHALL DISCHARGE TO EXTER-
 IOR OR TO PLUMBING FIXTURE.COUNTYWIDE
 AMENDMENTS 507.8.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.