| Plan Review Notes For Permit 00070484 |
| Permit Number |
00070484 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT A-1.0 FITTING RM #106 COMPLY | | | W/ FACBC 4.35, SWING OF DOOR IS IN | | | WHEEL CHAIR RADIUS,SWING DOOR OUT,ALSO | | | SHOW ELEVATION OF BENCH. | | | (2A) SHT P-1.0 SANITARY DIAGRAM, | | | HORIZONTAL DRY VENT NOT PERMITED SPC 94 | | | SEC 914.2 RECOMEND WET VENT SYSTEM. | | | SPC 94 SEC 911. | | | (B) WTR. HTR LOCATION TO BE READLY | | | ACCESSIBLE SPC 94 SEC 501.7,PROVIDE A | | | PERMINAMENT SHIPS LADDER AND WORKING | | | PLATFORM, TO COMPLY. | | | (C) NO CODE, MOP SINK IN PUBLIC REST RM | | | NOT RECOMENDED,PAST PRACTICE, LOCATE | | | MOP SINK IN JANITORS CLOSET. | | | )D) TOILET RM #2 DOOR SWINGS IN TURNING | | | RADIUS OF WHEEL CHAIR,SWING DOOR OUT, OR | | | MOVE LAV, FACBC4.16.2, ANOTHER GOOD | | | REASON TO RELOCATE MOP SINK. | | | (E) SHOW HEIGHT OF H/C WATER CLOSET ON | | | ELEVATIOPN DETAILS,SPC 94 SEC 104.2 | | | (F) SEE OTHER COMMENTS BY CPPR. | | | END OF COMMENTS |
|