Plan Review Notes
Plan Review Notes For Permit 00070484
Permit Number 00070484
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:
 1. FIRE DAMPERS REQUIRED AT RATED WALLS
 TO BE INDICATED.
 2.PROVIDE AN AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2..
 3.REQUIRE AN OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89..
 4.PROVIDE A GRILLE SCHEDULE ON PLANS.
 5.REQUIRE AN ENERGY EFFICIENCY RATING
 AS PER FLORIDA ENERGY EFFICIENCY CODE
 FOR THE AHU-1.
 6.PROVIDE A SMOKE DETECTOR IN RETURN
 DUCTWORK.