| Plan Review Notes For Permit 00070484 |
| Permit Number |
00070484 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1. FIRE DAMPERS REQUIRED AT RATED WALLS | | | TO BE INDICATED. | | | 2.PROVIDE AN AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2.. | | | 3.REQUIRE AN OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89.. | | | 4.PROVIDE A GRILLE SCHEDULE ON PLANS. | | | 5.REQUIRE AN ENERGY EFFICIENCY RATING | | | AS PER FLORIDA ENERGY EFFICIENCY CODE | | | FOR THE AHU-1. | | | 6.PROVIDE A SMOKE DETECTOR IN RETURN | | | DUCTWORK. |
|