Plan Review Notes
Plan Review Notes For Permit 00070483
Permit Number 00070483
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)MAX.OF 2 FIXTURES PERMITTED TO BE
 SUPPLIED BY 1/2"C.W.SIZE OF WATER SUPPLY
 TO WATER HEATER SHALL BE MIN.OF 3/4"PER
 COUNTY AMENDMENTS TO SPC 607.7.
  
 2)MIN.SIZE OF GREASE TRAP SHALL BE 750
 GALS.SEE ATTACHED.
  
 3)NO "M" COPPER U/G.SEE SHT.3,NOTE #11.
 COUNTYWIDE AMENDMENTS SEC.611.3.
  
 4)INDICATE TYPE OF PIPING FOR GAS SYSTEM
 AND SUBMIT MANUF.SHEETS FOR GAS EQUIP.
 ALL EQUIPMENT SHALL BE LISTED.SGC SEC.
 402.1.SEE ATTACHED LIST FOR GAS SYSTEM
 REQS.