| Plan Review Notes For Permit 00070483 |
| Permit Number |
00070483 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL | | | EQUIPMENT. YOU SHOW THE AIC FOR PANEL | | | BUT NEED THE MAINDISCONNECT RATING. | | | PER 110-9/215-5 | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% .(LIGHITNG) | | | | | | 3)NOTE: PLEASE SHOW ANY SIGN CIRCUIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAION FOR | | | REVIEW. PLANS WOULD HAVE PASSED WITH A | | | PROVISO BUT WERE COMING BACK FOR PLUMB | | | COMMENTS. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|