2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL
 EQUIPMENT. YOU SHOW THE AIC FOR PANEL
 BUT NEED THE MAINDISCONNECT RATING.
 PER 110-9/215-5
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% .(LIGHITNG)
  
 3)NOTE: PLEASE SHOW ANY SIGN CIRCUIT.
  
 PLEASE SUBMIT THE ABOVE INFORMAION FOR
 REVIEW. PLANS WOULD HAVE PASSED WITH A
 PROVISO BUT WERE COMING BACK FOR PLUMB
 COMMENTS. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  