| Plan Review Notes For Permit 00070456 |
| Permit Number |
00070456 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | THE PLUMBING IS APPROVED WITH THE | | | FOLLOWING PROVISOS.THIS INFORMATION MUST | | | BE SUBMITTED PRIOR TO PLUMBING INSPECT- | | | ION. | | | | | | 1)SUBMIT DETAIL OF WATER HEATER VENT. | | | INDICATE TYPE OF VENT(B,L,ETC.),TERM- | | | INATION POINT,LENGTH OF VENT CONNECTOR, | | | COMPLY W/SGC SEC.605.3,607.5,608.3. | | | | | | 2)DRAIN FOR BAR AREA(204)REQUIRES MIN.3" | | | VENT DOWNSTREAM OF ALL FIXTURES.(VENT IS | | | SHOWN ON P-1A BUT NOT ON RISER.) | | | | | | 3)GAS SYSTEM SHALL BE SIZED PER TABLE | | | 305.4(A) OF THE SGC.THERE IS NO TABLE | | | G102.5(1)IN THE GAS CODE OR PLBG.CODE. | | | REVISE TO COMPLY. | | | | | | 4)SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP. | | | EQUIPMENT SHALL BE LISTED.SGC 402.1,501. | | | | | | 5)SUBMIT DETAIL OF GAS MANIFOLD.PLANS | | | NOTE LOCATION IN TRANSFORMER ROOM. | | | MANIFOLD MAY REQUIRE RELOCATION FROM | | | SOURCE OF IGNITION PENDING INFORMATION. | | | | | | 6)DISHWASHER AND GARBAGE DISPOSAL SHALL | | | DISCHARGE TO THE SANITARY.SPC 409.5,, | | | 1004.11& CITY OF WPB ORD. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|