2001-01-08 00:00:001)THE MINIMUM NUMBER OF REQUIRED
 SANITARY FACILITIES SHALL COMPLY W/SPC
 TABLE 407.AN ADDITIONAL WATER CLOSET IS
 REQUIRED IN THE WOMEN'S RESTROOM.
  
 2)SIZE OF HANDICAP STALLS SHALL COMPLY
 W/FACBC SEC.4.17.3.(MIN.OF 83"WIDE REQD)
  
 3)SHT.A-12-CLEAR FLOOR SPACE UNDER H.C.
 LAV.SHALL BE 29"PER FACBC SEC.4.19.2.
  
 4)SEE ATTACHED LIST FOR GAS SYSTEM REQS.
  
 5)SUBMIT DETAIL OF WATER HEATER FLUE.
 COMPLY W/SGC 1997 EDITION.
  
 6)SHT.P-2-VENT SHALL CONNECT TO STACK
 VENT NOT 6"WASTE STACK.SPC SEC.901.2,
 904.1.
  
 7)DRY VENTS NOT PERMITTED PER SPC 906.2.
 SEE VENTS BY FIXTURES P-36,P-43-C,P-56,
 P-85,& H.C.WATER CLOSET IN TOILET ROOM.
  
 8)SIZE ALL SECTIONS OF THE SANITARY
 DRAIN ,WASTE AND VENT SYSTEM.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 9)SIZE ALL SECTIONS OF THE WATER RISER
 DIAGRAM.COUNTYWIDE AMENDMENTS TO SPC SEC
 104.2.1.
  
 10)FLOOR SINKS AND FLOOR DRAINS ARE NOT
 PROPERLY VENTED.SPC SEC.901.2.(SEE
 P-70B,9C,63B,P36,ETC.
  
 11)DISHWASHER AND GARBAGE DISPOSAL SHALL
 DISCHARGE TO SANITARY.SPC 409.5,1004.11.
 CITY OF WPB ORDINANCE.
  
 12)GAS SYSTEM SIZING IS NOT TO CODE.
 COMPLY W/SGC 305.4.
  
 13)POT/SCULLERY SINK SHALL BE STACKED &
 VENTED.SPC 713.1.
  
 14)WATER CLOSETS NOT PERMITTED ON WET
 VENTS.RELOCATE VENTS TO COMPLY W/COUNTY-
 WIDE AMENDMENTS TO SPC SEC.911.1.1.
  
 15)VACUUM RELIEF VALVE REQD.ON C.W.INLET
 TO GWH.
  
 16)HOT WATER TO RESTROOMS SHALL BE MAX.
 110 DEGREES PER FEC SEC.412.1ABCD.2.3.2.
  
 17)RESTAURANT SHALL COMPLY W/FLA.STATUTE
 553.141.(POTTY PARITY.)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.