Text |
| 2001-01-08 00:00:00 | 1)THE MINIMUM NUMBER OF REQUIRED |
| | SANITARY FACILITIES SHALL COMPLY W/SPC |
| | TABLE 407.AN ADDITIONAL WATER CLOSET IS |
| | REQUIRED IN THE WOMEN'S RESTROOM. |
| | |
| | 2)SIZE OF HANDICAP STALLS SHALL COMPLY |
| | W/FACBC SEC.4.17.3.(MIN.OF 83"WIDE REQD) |
| | |
| | 3)SHT.A-12-CLEAR FLOOR SPACE UNDER H.C. |
| | LAV.SHALL BE 29"PER FACBC SEC.4.19.2. |
| | |
| | 4)SEE ATTACHED LIST FOR GAS SYSTEM REQS. |
| | |
| | 5)SUBMIT DETAIL OF WATER HEATER FLUE. |
| | COMPLY W/SGC 1997 EDITION. |
| | |
| | 6)SHT.P-2-VENT SHALL CONNECT TO STACK |
| | VENT NOT 6"WASTE STACK.SPC SEC.901.2, |
| | 904.1. |
| | |
| | 7)DRY VENTS NOT PERMITTED PER SPC 906.2. |
| | SEE VENTS BY FIXTURES P-36,P-43-C,P-56, |
| | P-85,& H.C.WATER CLOSET IN TOILET ROOM. |
| | |
| | 8)SIZE ALL SECTIONS OF THE SANITARY |
| | DRAIN ,WASTE AND VENT SYSTEM.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 9)SIZE ALL SECTIONS OF THE WATER RISER |
| | DIAGRAM.COUNTYWIDE AMENDMENTS TO SPC SEC |
| | 104.2.1. |
| | |
| | 10)FLOOR SINKS AND FLOOR DRAINS ARE NOT |
| | PROPERLY VENTED.SPC SEC.901.2.(SEE |
| | P-70B,9C,63B,P36,ETC. |
| | |
| | 11)DISHWASHER AND GARBAGE DISPOSAL SHALL |
| | DISCHARGE TO SANITARY.SPC 409.5,1004.11. |
| | CITY OF WPB ORDINANCE. |
| | |
| | 12)GAS SYSTEM SIZING IS NOT TO CODE. |
| | COMPLY W/SGC 305.4. |
| | |
| | 13)POT/SCULLERY SINK SHALL BE STACKED & |
| | VENTED.SPC 713.1. |
| | |
| | 14)WATER CLOSETS NOT PERMITTED ON WET |
| | VENTS.RELOCATE VENTS TO COMPLY W/COUNTY- |
| | WIDE AMENDMENTS TO SPC SEC.911.1.1. |
| | |
| | 15)VACUUM RELIEF VALVE REQD.ON C.W.INLET |
| | TO GWH. |
| | |
| | 16)HOT WATER TO RESTROOMS SHALL BE MAX. |
| | 110 DEGREES PER FEC SEC.412.1ABCD.2.3.2. |
| | |
| | 17)RESTAURANT SHALL COMPLY W/FLA.STATUTE |
| | 553.141.(POTTY PARITY.) |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |