Plan Review Notes
Plan Review Notes For Permit 00070456
Permit Number 00070456
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:
 1.FIRE/SMOKE DAMPERS REQUIRED WHERE DUCT
 PENETRATES THE RATED WALLS.
 2.SEPERATE PERMIT REQUIRED FOR HOODS,GAS
 WALK-IN COOLER/FREEZER,FIRE SUPPRESSION
 SYSTEM.
 3.ENERGY EFFICIENCY RATING OF AHU,S
 REQUIRED PER FLORIDA ENERGY EFFICIECY
 CODE.
 4.EXHAUST FANS AND OUTSIDE AIR CLEARANCE
 PER 1997 SMC 506.1 SHOULD BE 10'(FT).
 5.CLEARANCE FROM BOTTOM OF SUPPORT BEAM
 TO THE TOP OF FINISHED ROOF, THE AHU
 STAND SHOULD BE 18" HEIGHT, NEEDS DETAIL
 OF STAND WHICH SHOULD BE SIGN & SEALED.
 6.DUCT MATERIAL SCHEDULE REQUIRED.