| 2001-01-08 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY |
| | THIS OFFICE. |
| | 2) PROVISIONS ARE TO BE MADE FOR AT |
| | LEAST TWO HANDICAPPED PERSONS. |
| | 3) INTERIOR FINISH ON WALLS AND CEILINGS |
| | SHALL BE CLASS A,B OR C. DOCUMENTATION |
| | ON FLAME SPREAD RATINGS ARE TO BE |
| | SUBMITTED ON DRAPERIES, SEATS AND OTHER |
| | ITEMS. |
| | 4) FIRE SPRINKLER DRAWING ON PAGE FS-1A |
| | DOES NOT SHOW FIRE SPRINKLER PROTECTION |
| | IN COOLER OR SHUTTER STORAGE. THE ENTIRE |
| | SPACE IS TO BE PROTECTED BY FIRE |
| | SPRINKLERS. THIS INCLUDES ALL COOLERS, |
| | FREEZERS, STORAGE, MECHANICAL, AND |
| | ELECTRICAL ROOMS. |
| | 5) WHERE IS THE EMERGENCY LIGHTING FOR |
| | THE OUTSIDE DINING AREA (201). |
| | 6) ANY CHANGES IN ELEVATIONS LESS THAN |
| | 21 INCHES,SHALL BE BY RAMPS. |
| | 7) ANY DOOR USED FOR EXITING MUST BE |
| | EQUIPPED WITH APPROVED PANIC HARDWARE. |
| | FIRE DOORS ARE TO BE EQUIPPED WITH |
| | APPROVED FIRE EXIT PANIC HARDWARE. |
| | 8) PROVIDE DETAILS ON PIZZA OVEN. |
| | 9) PROVIDE COMPLETE HOOD,DUCT AND FIRE |
| | EXTINGUISHING PLANS TO BUILDING DEPT. |
| | SEPARATE PERMITS REQUIRED. |
| | 10) MAIN FIRE EXIT MUST BE CAPABLE OF |
| | EXITING AT LEAST 50 PERCENT OF THE |
| | OCCUPANT LOAD. |
| | 11) NO WAITING SPACE CALCULATIONS |
| | INCLUDED IN SEATING TABULATIONS. |
| | 12) PROVIDE COMPLETE SHOP DRAWINGS FOR |
| | THE INSTALLATION OF FIRE ALARM EQUIPMENT |
| | SHOWN ON DRAWINGS. |
| | 13) PORTABLE FIRE EXTINGUISHERS REQUIRED |