| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: OUTLET IN WINE ROOM STORAGE TO | | | BE GFI/ GFI PROTECTED PER 210-8-A-8 | | | | | | 2)NOTE : PER 210-63 GFI OUTLET FOR | | | ROOF TOP EQUIPMENT 25`. | | | | | | 3)NOTE: PLEASE NOTE PANEL"A" NEEDS TO BE | | | MCB. REQ`D MAIN ON LOAD SIDE OF TRANS- | | | -FORMER. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|