2001-01-08 00:00:001. FLORIDA ENERGY CALUCATIONS MUST BE
 SIGNED BY OWNER/AGENT.
 2. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR STOREFRONT WINDOWS
 AND DOORS. METRO DADE COUNTY OD SBBCI
 STTD12-97.
 3. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS. FIRE SPRINKLER PERMIT TO BE
 ISSUED PRIOR TO ISSURANCE OF BUILDING
 PERMIT.
 4.EXISTING FIRE RATED DEMISING WALL- 2HR
 FIRE RATED SEPERATION REQUIRED- PROVIDE
 UL NUMBER-NOTE DETAIL 7 ON SHEET A-12
 TENANT SIDE SHOWS BEING COMPLETED BY
 T.G.C. BOTH SIDES TO BE COMPLETED PRIOR
 TO C.O. BEING ISSUED.
 5. SHOW ARANGEMENT AND NUMBER OF EXITS
 COMPLY WITH 1997 SBC CHAPTER 10
 SECTION 1004.
 6. SHOW THAT BAR AREA COMPLIES WITH
 1997 SBC CHAPTER 10 SECTION 1019.8
 STAIRWAY CONSTRUCTION.
 7. LIST GOVERNING CODES ON COVER SHEET.
 8. BUILDING IS TYPE 2 CONSTRUCTION 1997
 SBC ALL WOOD FRAMING SHALL COMPLY WITH
 CHAPTER 6&7.