| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY CALUCATIONS MUST BE | | | SIGNED BY OWNER/AGENT. | | | 2. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT GLAZING FOR STOREFRONT WINDOWS | | | AND DOORS. METRO DADE COUNTY OD SBBCI | | | STTD12-97. | | | 3. SUBMIT FIRE SPRINKLER APPLICATION AND | | | PLANS. FIRE SPRINKLER PERMIT TO BE | | | ISSUED PRIOR TO ISSURANCE OF BUILDING | | | PERMIT. | | | 4.EXISTING FIRE RATED DEMISING WALL- 2HR | | | FIRE RATED SEPERATION REQUIRED- PROVIDE | | | UL NUMBER-NOTE DETAIL 7 ON SHEET A-12 | | | TENANT SIDE SHOWS BEING COMPLETED BY | | | T.G.C. BOTH SIDES TO BE COMPLETED PRIOR | | | TO C.O. BEING ISSUED. | | | 5. SHOW ARANGEMENT AND NUMBER OF EXITS | | | COMPLY WITH 1997 SBC CHAPTER 10 | | | SECTION 1004. | | | 6. SHOW THAT BAR AREA COMPLIES WITH | | | 1997 SBC CHAPTER 10 SECTION 1019.8 | | | STAIRWAY CONSTRUCTION. | | | 7. LIST GOVERNING CODES ON COVER SHEET. | | | 8. BUILDING IS TYPE 2 CONSTRUCTION 1997 | | | SBC ALL WOOD FRAMING SHALL COMPLY WITH | | | CHAPTER 6&7. |
|