| 2001-01-08 00:00:00 | 1) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON DRAWINGS. | | | 2) FITTING ROOM AND BATHROOM DOORS | | | CANNOT INTERFERE WITH ACCESS TO EXIT | | | DOOR LEADING INTO STOCKROOM. | | | 3) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS EXIST, | | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS THROUGH STOCKROOM, THE DOOR LEADING | | | TO STOCKROOM CANNOT BE LOCKED, AISLE | | | OF AT LEAST 44" WIDE BE PRESENT WITHIN | | | STOCKROOM, THIS 44" AISLE BE MAINTAINED. | | | 4) PORTABLE FIRE EXTINGUISHERS ARE | | | REQUIRED. |
|