Plan Review Notes
Plan Review Notes For Permit 00070350
Permit Number 00070350
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PROVISO::::::::
  
 1. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TIED TO BUILDING FIRE ALARM OR
 HORN AND STROBE PER NFPA 90A 4-4.4