| Date |
Text |
| 2001-01-08 00:00:00 | |
| | |
| | |
| | |
| | |
| | 1. PROVIDE SIGNED AND SEALED FLORIDA |
| | ENERGY SHEETS, 1997 EDITION |
| | 2. FIRE SPRINKLER PERMIT REQUIRED PRIOR |
| | TO ISSURANCE OF BUILDING PERMIT. |
| | 3. EXTERIOR SIGNS REQUIRE SEPRATE PERMIT |
| | 4. SUBMIT APPROVAL FROM SPECIAL |
| | INSPECTOR. |
| | 5. EXTERIOR GLAZING: PROVIDE PRODUCT |
| | APPROVAL SHEETS, METRO DADE COUNTY |
| | OR SBC 1997 SSTD 12-97 |
| | 6. ALL WOOD FRAMING TO BE FIRE RETARDANT |
| | LUMBER AS PER SBC 1997 CHAPTERS 6&7 |
| | 7. HANDICAP FITTING ROOM: DOOR SHALL NOT |
| | SWING INTO TURNING RADIUS, FLORIDA |
| | ADA SECTION 4.35.2 |
| | 8. PAGE 1: PROJECT DATA CODE REQUIREMENT |
| | REVISE NEC 1996 TO NEC 1999. |
| | 9. TENTANT SEPERATION TO MEET SBC 1997 |
| | TABLE 704.1 OCCUPANCY SEPERATION |
| | REQUIREMENTS.( BOTH SIDES MUST BE |
| | COMPLETED PRIOR TO C.O.) |
| | 10. SHUTTERS ARE INDICATED ON DETAIL14 |
| | SHEET 7, PROVIDE PRODUCT APPROVAL |
| | INFORMATION SHEETS,INDICATE AREA OF |
| | STORAGE, SHOULD SHUTTERS BE STORED ON |
| | END SHUTTERS SHALL BE DESIGNED FOR |
| | ADDITIONAL LOADING; PROVIDE LETTER |
| | FROM TENTANT AS WHO WILL INSTALL AND |
| | TIME NEED TO INSTALL FOR APPROVAL OF |
| | BUILDING OFFICAL. |