| Plan Review Notes For Permit 00070350 |
| Permit Number |
00070350 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1.PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89. | | | 2.PROVIDE ENERGY EFFICIENCY RATING OF | | | THE AIR AHU AS PER FLORIDA ENERGY | | | EFFICIENCY CODE. | | | 3.PROVIDE AN AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2.. | | | 4.REQUIRED FIRE AT RATED WALLS WHERE | | | APPLICABLE. | | | 5.REQUIRED AHU , DUCTWORK AND DIFFUSER | | | MOUNTING DETAIL ON PLANS. | | | 6.PROVIDE DUCT MATERIAL SCHEDULE. | | | 7.EXHAUST FANS SCHEDULE REQUIRED. |
|