2001-01-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 2.PROVIDE ENERGY EFFICIENCY RATING OF
 THE AIR AHU AS PER FLORIDA ENERGY
 EFFICIENCY CODE.
 3.PROVIDE AN AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2..
 4.REQUIRED FIRE AT RATED WALLS WHERE
 APPLICABLE.
 5.REQUIRED AHU , DUCTWORK AND DIFFUSER
 MOUNTING DETAIL ON PLANS.
 6.PROVIDE DUCT MATERIAL SCHEDULE.
 7.EXHAUST FANS SCHEDULE REQUIRED.