| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) SPRINKLER HEADS SHOWN BUT NO PIPING | | | OR HYDRAULIC CALCULATIONS PROVIDED. SOME | | | AREAS APPEAR TO BE NOT PROPERLY | | | PROTECTED BY FIRE SPRINKLERS. | | | 2) TRANSFORMER IN REAR OF STORE SHOULD | | | BE RELOCATED. ALTHOUGH 44" WIDTH IS | | | CODE ALLOWABLE, THE TRANSFORMER BECOMES | | | A PERMANENT OBSTACLE. | | | 3) HOW IS THE BASE BUILDING FIRE ALARM | | | SYSTEM HEARD IN TENANT SPACE WHEN | | | ACTIVATED. |
|