| Plan Review Notes For Permit 00070350 |
| Permit Number |
00070350 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************ UNSAT ******************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING) AND INCULDE SHOW WINDOW AND | | | TRACK LIGHTING LOADS PER 220-12(A,B) | | | | | | 2)NOTE:PLEASE NOTE THAT YOU SHOW GROUND- | | | -ING ELECTRODE REF. ART 250-26, PLEASE | | | SIZE PER ART 250-66 | | | | | | 3)NOTE: PLEASE SUBMIT SOME CLARIFICATION | | | ON HVAC UNIT LOAD? YOU SHOW 2992VA WHERE | | | IS THIS LOAD COMING FROM.? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTION | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|