| Plan Review Notes For Permit 00070261 |
| Permit Number |
00070261 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | PROVIDE LOCATION AND DETAILS OF DAMPERS | | | AT RATED WALLS AS PER 1997 SMC 610.1.2.. | | | REQUIRE AIR BALANCE SCHEDULE PER 1997 | | | SMC 501.2.. | | | PROVIDE OUTSIDE CALCULATION AS PER | | | ASHRAE 62-89.... | | | PROVIDE EER RATING OF AHU AS PER FLORIDA | | | ENERGY EFFICIENCY CODE,SMOKE DETECTOR | | | IN DUCT, FAN SHUTDOWN AS PER NFPA 90A | | | 4.4.4.2 & 4.4.4.3... | | | PROVIDE AHU MOUNTING DETAIL. | | | REQUIRE DUCT MOUNTING DETAIL AND DIFFU- | | | SER, FLEX CONNECTION DETAIL REQUIRED. |
|