2001-01-08 00:00:00DENIED:
 PROVIDE LOCATION AND DETAILS OF DAMPERS
 AT RATED WALLS AS PER 1997 SMC 610.1.2..
 REQUIRE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2..
 PROVIDE OUTSIDE CALCULATION AS PER
 ASHRAE 62-89....
 PROVIDE EER RATING OF AHU AS PER FLORIDA
 ENERGY EFFICIENCY CODE,SMOKE DETECTOR
 IN DUCT, FAN SHUTDOWN AS PER NFPA 90A
 4.4.4.2 & 4.4.4.3...
 PROVIDE AHU MOUNTING DETAIL.
 REQUIRE DUCT MOUNTING DETAIL AND DIFFU-
 SER, FLEX CONNECTION DETAIL REQUIRED.