2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH SPRINKLER DRAWINGS.
 2) AN ADDITIONAL EMERGENCY LIGHT
 REQUIRED IN MAIN FLOOR AREA.
 3) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 4) EXITING THROUGH STOCKROOM ALLOWED
 ONLY IF, NOT MORE THAN 50 PERCENT OF
 EXIT ACCESS PERMITTED, DOOR LEADING
 TO STOCKROOM CANNOT BE LOCKED, AISLE
 USED FOR EXITING SHALL BE AT LEAST
 44" WIDE, AND AISLE TO REMAIN IN
 UNOBSTRUCTED CONDITION.
 5) A PORTABLE FIRE EXTINGUISHER WITH
 A CURRENT SERVICE TAG IS TO BE
 PROVIDED.