| Plan Review Notes For Permit 00070261 |
| Permit Number |
00070261 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH SPRINKLER DRAWINGS. | | | 2) AN ADDITIONAL EMERGENCY LIGHT | | | REQUIRED IN MAIN FLOOR AREA. | | | 3) INTERIOR FINISH SHALL BE CLASS A OR | | | B. | | | 4) EXITING THROUGH STOCKROOM ALLOWED | | | ONLY IF, NOT MORE THAN 50 PERCENT OF | | | EXIT ACCESS PERMITTED, DOOR LEADING | | | TO STOCKROOM CANNOT BE LOCKED, AISLE | | | USED FOR EXITING SHALL BE AT LEAST | | | 44" WIDE, AND AISLE TO REMAIN IN | | | UNOBSTRUCTED CONDITION. | | | 5) A PORTABLE FIRE EXTINGUISHER WITH | | | A CURRENT SERVICE TAG IS TO BE | | | PROVIDED. |
|