2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE:PLEASE INSTALL MAIN DISC INLINE
 FROM BLD ELEC ROOM IN TENANT SPACE WITH
 TENANT EQUIPMENT.
  
 2)NOTE: PLEASE SEE TABLE 450-3B FOR
 CLARIFICATION ON MAIN BRKR RATING.
  
 3)NOTE: MORE THAN ONE WIRE SIZE IS SHOWN
 COMING FROM BLD ELECTRICAL ROOM TO
 TENANT SPACE??? PLEASE CLARIFY. SIZE PER
 310-16.
  
 4)NOTE: PLEASE INCLUDE TRACK LIGHTING
 IN LOAD CALCULATIONS/ PLEASE SHOW PER
 220-12B
  
 5)NOTE:PLEASE NOTE THAT RISER SHOWS
 125A MCB AND PANEL "L" SHOWS 100A MCB?
 PLEASE ADJUST.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REIVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELETRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372