Plan Review Notes
Plan Review Notes For Permit 00070108
Permit Number 00070108
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH DEPT.FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 2)NUMBER OF WATER CLOSETS IN WOMEN'S RR
 SHALL COMPLY W/TABLE 407 OF SPC.ED ON
 THE OCCUPANT LOAD.
  
 3)OVERFLOW REQD.ON CONDENSATE TO DRYWELL
 TO ENSURE PROPER OPERATION/MAINTENANCE
 OF SYSTEM.SMC SEC.304.8.3,SPC SEC.301.4.
  
 4)PROTECTION AGAINST HAZARD AND NOISE IN
 THE WATER DISTRIBUTION SYSTEM SHALL
 COMPLY W/SPC 607.8.3.CALCULATED AIR
 CHAMBERS SHALL BE EQUIPPED W/METHOD OF
 RECHARGING AND BE ACCESSIBLE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.