| Plan Review Notes For Permit 00070108 |
| Permit Number |
00070108 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | | | | | | | | | | THE SPACE IS RECEIVING 5250 CFM OF | | | OUTSIDE AIR AND IS REMOVING VIA EXHAUST | | | FANS A TOTAL OF 5550 CFM. THIS WOULD PUT | | | THE SPACE IN A NEGATIVE CONDITION ACCORD | | | ING TO THE PLAN. FLORIDA ENERGY CODE | | | DOES NOT ACCEPT THIS CONDITION. ADJUST | | | VOLUME TO POSITIVE OR NEUTRAL CONDITION. | | | WITH THE RELIEF FAN. |
|