| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 2. DUCT SMOKE DETECTOR TO BE TIED TO | | | HORN AND STROBE IF NO BLDG FIRE ALARM | | | FOR NOTIFICATION PER NFPA 90A 4-4.4 | | | NOTE: EXHAUST FANS TIED TO SWITCH SHALL | | | NOT BE USED AS PART OF AIR BALANCE SCHED | | | ULE REQUESTED ABOVE |
|