2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 SHOWING THE 125% FOR ALL CONTINUOUS LOAD
 PLEASE SHOW SQ. FT FOR LOAD CALCS.
  
 2)NOTE: PLEASE NOTE THAT AIC RATINGS ARE
 SUBMITTED FOR PANELS, BUT STILL NEED TO
 PROVIDE AIC RATING FOR MAIN DISCONNECT.L
 AIC RATINGS ARE TO BE SUBMITTED FOR ALL
 EQUIPMENT BEING INSTALLED. 110-9
  
 3)NOTE: PIPE FROM MAIN DISCONNECT TO
 PANELS SHOW NO EQUIPMENT GROUNDING COND-
 --UCTOR? IS THIS RIGID?PLEASE CLARIFY
  
 4)NOTE: PLEASE SHOW ALL LOADING FOR
 TRACK LIGHTING PER 220-12B
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  