| Plan Review Notes For Permit 00070108 |
| Permit Number |
00070108 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS | | | SHOWING THE 125% FOR ALL CONTINUOUS LOAD | | | PLEASE SHOW SQ. FT FOR LOAD CALCS. | | | | | | 2)NOTE: PLEASE NOTE THAT AIC RATINGS ARE | | | SUBMITTED FOR PANELS, BUT STILL NEED TO | | | PROVIDE AIC RATING FOR MAIN DISCONNECT.L | | | AIC RATINGS ARE TO BE SUBMITTED FOR ALL | | | EQUIPMENT BEING INSTALLED. 110-9 | | | | | | 3)NOTE: PIPE FROM MAIN DISCONNECT TO | | | PANELS SHOW NO EQUIPMENT GROUNDING COND- | | | --UCTOR? IS THIS RIGID?PLEASE CLARIFY | | | | | | 4)NOTE: PLEASE SHOW ALL LOADING FOR | | | TRACK LIGHTING PER 220-12B | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | 561-659-8096 EXT 8372 |
|